BUILDING CODE COMMISSION DECISION ON B.C.C. #93-1-357

IN THE MATTER OF BUT NOT LIMITED TO: Ontario Building Code, O/Reg. 413/90 as amended

PARTS, 11.2.2.1. and 3.2.9.3.
New Building Systems and F.H.C. water supply

COMMISSION RULING:

In favour of the Respondent

Regarding Ottawa Hunt & Golf Club, 3811 Bowesville Road, Ottawa, Ontario.

It is the decision of the Building Code Commission that this matter of extending standpipe and F.H.C. system to serve the new additional rooms and floor areas shall require a fire pump and generator to meet the requirements of the Code. Measures shall also be taken to prevent backflow into the potable water supply system. A siamese connection and supervision be added to the standpipe system.

REASONS:

The new construction is required to comply with Part 3 of the Ontario Building Code.